Acoustic calculation

Acoustics

Fan noise by octave band and its attenuation along the run to the point of interest.

Acoustic calculation

Ventilation noise level in a room, to SN 2.2.4/2.1.8.562-96

Noise source

Network components

m
off
off
Total attenuation through the network:17.0 dB

Room

Results

Requirements are met

Noise level at the workstation: 39.8 dB(A)

Limit for Private office: 45 dB(A)

Octave spectrum

63
125
250
500
1000
2000
4000
8000
Permissible level 45 dB(A)
Frequency, Hz631252505001000200040008000
Fan7976747269656259
Indoors4441393734302724
dB(A)1825313434322823

Help

dB(A) — A-weighted sound level, matched to the response of human hearing.

Octave bands — frequency bands for noise analysis (63–8000 Hz).

Calculated to SN 2.2.4/2.1.8.562-96 “Noise in the workplace”.